Outage Time Change 11:30PM Oct 6th – 1AM Oct 7th

Due to updated info from Isomedia, we will be starting shutdown of our equipment at 11:30PM.  Work is expected to start at midnight and be completed by 12:30 and it will take about half an hour to bring all of our servers back up.  Below is the notice we received from Isomedia.

I have to say that while I’m not happy about the failure, I am happy that Isomedia both regularly tests their equipment and keeps their customers informed.  Our previous provider did neither.

This is a REMINDER of work happening tonight at our Eastgate Data Center.

Tonight between 12AM - 2AM 
Electricians complete the cutover of power service to the new transformer. 
THIS WILL CAUSE A PLANNED POWER DISRUPTION TO CUSTOMERS.  We expect the
disruption in power to be relatively short ~30 minutes.  We strongly
recommend all customer equipment be safely powered down prior to the start
of this work.  If you are unable to complete this remotely and are unable to
be onsite Data center technicians will be available to assist in powering
off or powering on equipment.  This step will also isolate the old UPS and
allow for the physical removal of the unit from the facility.  

If you need assistance during the Monday night event please reply to this
email with details on what you would like us to help with.  We apologize in
advance for any inconvenience caused by this event. Further updates will be
made available via ISOMEDIA's network status page at
http://www.isomedia.com/support-network-status.shtml. 


Below is the original notice sent last week

-------------------------


As mentioned previously, last Friday evening the Eastgate UPS encountered
error conditions resulting in the need to switch power into bypass. The
manufacturer (Eaton) has confirmed failures with the internal inverter and
rectifier of the UPS.  Eaton recommended we move forward in installing a new
UPS we had staged in an adjacent space for future expansion.  This work is
significant and as such is being completed in stages to ensure there is no
unexpected impact to customers.  Electricians started work Monday on the
installation of new conduit and electrical service to prepare for the new
UPS and transformer installation. The schedule at this time is as follows:

-Monday Afternoon - October 6th
A new upgraded electrical transformer will be set and connections made to a
new bypass panel.

-Monday Evening/Tuesday Morning 12AM-2AM - October 7th
Electricians complete the cutover of power service to the new transformer. 
THIS WILL CAUSE A PLANNED POWER DISRUPTION TO CUSTOMERS.  We expect the
disruption in power to be relatively short ~30 minutes.  We strongly
recommend all customer equipment be safely powered down prior to the start
of this work.  If you are unable to complete this remotely and are unable to
be onsite Data center technicians will be available to assist in powering
off or powering on equipment.  This step will also isolate the old UPS and
allow for the physical removal of the unit from the facility.  

-Tuesday Afternoon - October 7th
Electricians will connect the new UPS to the new bypass panel and power.

-Wednesday Morning - October 8th
Eaton will be onsite to complete the startup process and testing of the new
UPS. 

-Wednesday Afternoon - October 8th
Technicians will route power service to the new UPS.  This will restore
Eastgate's emergency power systems to fully working conditions.  

---

These time estimates are based on several external factors and technician
expectations.  Although not expected, there is a chance that these estimates
may change as work is completed.  If anything changes we will notify
customers with new expectations.

Other than the transformer cutover Tuesday morning at 12AM there is NO
expectation of disruptions in power to the data center or customer
equipment.  However, until the new UPS is in service the Eastgate Data
Center is not fully protected from a power disruption.  In the case of a
power event the emergency generator will start but there would be a brief
disruption as automatic systems switch power to the genset.

If you need assistance during the Monday night event please reply to this
email with details on what you would like us to help with.  We apologize in
advance for any inconvenience caused by this event. Further updates will be
made available via ISOMEDIA's network status page at
http://www.isomedia.com/support-network-status.shtml. 

Sincerely,
ISOMEDIA Inc.